Cooling Tower water Pump
hydrogen boiler infrared thermal imaging hydrogen boiler visible light
Infrared Thermal Image Visible Light Image
This A phase wire connection was showing 367 degrees. We locked out the machine and pulled the wire. We then cleaned it and reinstalled it making sure all wire connections were tight. Then placed machine back in service. We let it run all night and checked it again at noon the next day and the temperature was just under 144 degrees. A work order to replace the wire has been generated and this will take place at the next shut down.
 
Potential savings of approximatly $22,000 in equipment alone, much less the down time without this machine.